Permit: T02EL00841

Parcel: 135023550

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/10/2002 ELECTRIC - SERVICE UPGRADE Approved
08/01/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0930*
06/14/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0210*1.) THE GROUNDING OF THE ELECTRIC SERVICE MUST INCLUDE TWO 5/8 X 8' GROUND RODS DRIVEN TO 2" BELOW GROUND LEVEL AND SET NOT CLOSER THAN 6' FT APART. A # 6 BARE (SOLID) COPPER CONDUCTOR SHOULD BE USED TO CONNECT THESE TO THE PANEL. 2. LEAVE A COPY OF THE PERMIT BUILDING PERMIT FOR THE WORK OF ENCLOSING THE REAR PORCH. THANKS FLAG THE GROUND RODS FOR EASY LOCATION AT INSPECTION. USE ACORN STYLE CLAMPS.