Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 05/09/2002 |
ELECTRIC - RECONNECT |
|
Approved |
OK TO CLEAR RECONNECT. |
| 05/07/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999* PLEASE COMPLY WITH THE ABOVE BEFORE THE NEXT INSPECTION. HAVE LICENSED L-11 CONTRACTOR CALL 791-5550 EXT 136 NEED NAME AND NUMBER OF L-11. |
| 04/24/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*1.) THE GROUNDING ELECTRODE SYSTEM (AT SERVICE) HAS BEEN CUT OFF. A NEW GROUND SYSTEM WILL BE REQUIRED, TO INCLUDE 2 RODS, WATER, FRAME AND GAS BOND. 2.) THE USEAGE WILL BE AUTOMOTIVE REPAIR, WROUGHT IRON AND WOOD DOOR MANUFACTURING. WILL NEED A COMPLETE C OF O INSPECTION OBTAIN A PERMIT FOR C OF O. WITH ABOVE STATED USEAGE(SEE #2.) OR PROVIDE LAST CERTIFICATE OF OCCUPANCY INDICATING THE USEAGE PER #2 ABOVE. 3.) INSTALL FILLER PLATER 4.) MAXIMUM BREAKER FOR PANEL FEEDER IN 90 AMP 5.) AN L-11 CONTRACTOR REQUIRED TO DO WORK. |