Permit: T02EL00803

Parcel: 136212310


Addresses:

7451 E 38TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/18/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR.
04/23/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0215*THANKS 1.)THE NIPPLE BETWEEN METER CAN AND PANEL MUST BE BONDED. USE BONDING BUSHING BOTH SIDES. 2.) THE GAS PIPE MUST BE BONDED TO THE UFER. BOND IT WHERE IT ENTERS THE HOUSE WALL. 3.) YELLOW TAPE IS NOT APPROVED FOR IDENTIFYING THE NEUTRAL/GROUNDED CONDUCTOR. USE WHITE. 4.) ALWAYS LEAVE YOUR INSPECTION RECORD SHEEET CARD ON SITE.