Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR. |
| 04/23/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0215*THANKS 1.)THE NIPPLE BETWEEN METER CAN AND PANEL MUST BE BONDED. USE BONDING BUSHING BOTH SIDES. 2.) THE GAS PIPE MUST BE BONDED TO THE UFER. BOND IT WHERE IT ENTERS THE HOUSE WALL. 3.) YELLOW TAPE IS NOT APPROVED FOR IDENTIFYING THE NEUTRAL/GROUNDED CONDUCTOR. USE WHITE. 4.) ALWAYS LEAVE YOUR INSPECTION RECORD SHEEET CARD ON SITE. |