Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL00796
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
05/29/2002 | ELECTRIC - FINAL | Not ready for Inspection | CONTRACTOR NOT IN COMPLIANCE WITH LST WRITE UP OF 5-7-02. PLEASE MAKE CORRECTION AND RECALL INSPECTION | |
05/07/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0210*1.) MUST USE #4 CU. MIN. FOR GROUNDING SYSTEM BECAUSE OF VULNERABILITY TO PHYSCIAL DAMAGE 2.) PLEASE STRAITEN OUT GROUND WIRE AND ADD MORE STRAPS, USE PLATED SCREWS IN LIEU OF DRYWALL SCREWS 250-64 (B) OTHER DISCRAPANCIER WERE APPROVED THROUGH THE APPEALS PROCESS. | |
04/22/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*1.) NO INFORMATION REGARDING WORK, LOCATION, ETC. 2.) NO OWE ONE SITE STORE CLOSED 8: AM RECALL. |