Permit: T02EL00795


Addresses:

799 E 6TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL00795

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/08/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000* OK TO CLEAR ECO.
04/25/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*MULTIPLE CONDUCTOR CONNECTED TO ACORN TYPE OF ROD CLAMP IS NOT PERMITTED DOUBLE LUGGING AT GROUND TERMINAL NOT PERMITTED. MULTIPLE CONDUCTOR IN AN TERMINATION SLOT. REINSPECTION FEE DUE
04/22/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) INSTALL GROUND CLAMP AS PER MANUFACTURES INSTRUCTIONS 2.) WE HAVE MULTIPOLE TERMANATION AT GROUND CLAMP AND UNDER LUGS. 3.) BONDING JUMPER TO BE SIZED AS PER CODE.