Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/22/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/19/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0165*CITY CODE REQUIRES EACH BEDROOM TO HAVE A SMOKE DETECTOR INSTALLED. BATTERY OPERATED UNITS ARE ALLOWED. PLEASE INSTALL PER MANUFACTURERS INSTRUCTIONS AND RECALL THIS INSPECTION. THANKS. |