Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/19/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 04/17/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) PATCH HOLE IN ROOF ABOVE NEW SERVICE ENCLOSURE. 110-12 NEC. 2.) NEED TO INSTALL BUSHING IN BACK KO FOR PROTECTION AGAINST ABRASION OF BRANCH CIRCUITS. 300-15 NEC. 3.) 2 GROUND RODS REQUIRED 6' MIN APART. PER 250-52 NEC. 4.) BOND GAS PIPE 250-104 NEC. 5.) RECEPTACLE BELOW SERVICE TO BE GFI. |