Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/25/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/19/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*SCH-40 PVC NOT ALLOWED, MUST BE SCH-80 OR EMT, PER #9287 CITY ORDINANCE, 2.) NEW DRYER CIRCUIT TO BE 4 WIRE CIRCUIT PER 250-140 NEC. 3.) INSTALL BUSHING IN KO, BACK OF SUB PANEL TO PROTECT CABLE FROM ABRASION (OUTDOOR). 4.) LABEL BREAKER IN SUB-PANEL. OUTDOOR. 5.) BOND GAS PIPING 250-104 NEC. |