Permit: T02EL00761

Parcel: 116141450

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/23/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR.
04/22/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1.) 1/4" MININUM HARDWARE IS NEEDED FOR RISER STRAP AS #4 STATED. 2.) PLEASE PROVIDE A SEALING DEVICE FOR THE CONDUIT ENTRY ABOVE THE BUS.
04/17/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1.) GROUND RODS CAN NOT BE BENT OVER, PLEASE INSTALL AS PER CODE 250-52. 2.) FINISH INSTALLING CONDUIT RUNS. 3.) A PERMANENT METAL ADDRESS LABEL IS NEEDED 4.) A STRAP IS NEEDED FOR THE RISER ABOVE THE PANEL. PLEASE USE 1/4" MIN HARDWARE. 5.) VERTICAL CLEARENCE FROM GROUND NEED TO MEET CODE 230-24 (B) BW ELECTRIC IS DOING WORK.