Permit: T02EL00754

Parcel: 117033570


Addresses:

604 E UNIVERSITY BL


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T02EL00754

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
04/19/2002 ELECTRIC - SERVICE UPGRADE Approved
04/17/2002 ELECTRIC - SERVICE UPGRADE Denied 1.) INSTALL TWO SUPPORTS FOR THE RISER PIPE BELOW THE ROOF LEVEL. 2.) ANCHOR THE UNISTRUT WITH THRU-BOLTS OR OTHER SOLID ANCHORING METHOD. USE SPACERS TO PREVENT THE UNISTRUT FROM PULLING AWAYS. FROM SUPPORT WALL SURFACE. 3.) THE CUT OVER OF THE EXISTING PANELS OR CIRCUITS SHOULD BE INCLUDED IN THE PERMIT, AND INSPECTION OF CONDUIT RUNS AND WIRING SHOULD BE REQUESTED.