Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/25/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 06/12/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*PLEASE COMPLETE ITEM #2 OF PREVIOUS INSPECTION. |
| 05/20/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) NEED PERMANENT METAL ADDRESS TAG. 2.) SERVICE PANEL BOARD IN VIOLATION OF 99 NEC. 110-26. WATER LINER BELOW PANEL BOARD) ALSO 30" WIDE X 36" CLEAR FRONTAL AREA. 3.) LOOSE CONNECTORS 4.) RISER IS CROOKED 5.) INSTALLED 20 AMP BREAKER FOR 15 AMP CIRCUIT. 6.) GROUND RODS MUST BE A MINMUM OF 6FT APART. 7. PLEASE GROUND WIRE APROX. THANKS 6". |