Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 05/03/2002 |
ELECTRIC - RECONNECT |
|
Approved |
|
| 04/26/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL PERMANENT ADDRESS NEC 230-70 LABEL. 2.) BUSHING REQUIRED ON BACK KO TO PROTECT CABLE FROM ABRASION. NEC 300-15C. 3.) SUPPORT RISER WITHIN 3' OF ENCLOSURE 4.) I.D. CIRCUIT BREAKER 5.) 2 GROUND RODS REQUIRED 6' MIN APART, PER 250 NEC. 6.) BOND GAS LINE. PER 250 NEC. 7.) LEAVE NAME, PH# OF LICENSED CONTR. DOING WORK. |
| 04/25/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0920* |