Permit: T02EL00743

Parcel: 132180220


Addresses:

1201 E TENNESSEE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/30/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*POWER CLEARANCE SUBJECT TO VERIFICATION OF APPROVAL OF ROOF TOP HVAC SYSTEM. CALL 791-5550 X 323. AND LEAVE PERMIT AND NAME OF LICENSED MECHANICAL CONTRACTOR.
04/23/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*GROUND WIRE TO BE IN WEDGE OF ACORN CLAMP. BREAKER MUST BE CUTLER HAMMER. @ SUB PANEL. REMOVE BONDING STRAP AND INSTALL AND EQUIPMENT GROUND BAR, USE SUITABLE GROUND KIT AS PER LISTING. INSTALL FILLER PLATER AND K.O. SEALS.