Permit: T02EL00711

Parcel: 137070470

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL00711

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/30/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/21/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*LOW VOLTAGE WIRING IN CEILING USED TO CONVERY ENVIRONMENTAL AIR MUST BE RATED FOR SUCH. PLEASE SHOW MANUFACTURER U.L. LISTING TO IDENTIFY THAT WIRING IS PLENUM RATED.
ATTACHMENT OF LOW VOLTAGE CONTROLLER IS IMPROPER. TAPE AS A FASTENING MEANS IS UNACCEPTABLE AND THERE ARE NO BUSHINGS TO PROTECT THE HIGH VOLTAGE WIRING.