Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/21/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*LOW VOLTAGE WIRING IN CEILING USED TO CONVERY ENVIRONMENTAL AIR MUST BE RATED FOR SUCH. PLEASE SHOW MANUFACTURER U.L. LISTING TO IDENTIFY THAT WIRING IS PLENUM RATED. ATTACHMENT OF LOW VOLTAGE CONTROLLER IS IMPROPER. TAPE AS A FASTENING MEANS IS UNACCEPTABLE AND THERE ARE NO BUSHINGS TO PROTECT THE HIGH VOLTAGE WIRING. |