Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/22/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/18/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 04/10/2002 |
ELECTRIC - FINAL |
|
Denied |
1. ELECTRICAL SERVICE UPGRADE IS REQUIRED BY ARIZ ST LAW TO BE DONE BY A LICENSED C-11 ELECTRICAN, PLEASE PROVIDE A LETTER BY CONTRACTOR DOING THIS WORK SERVICE HOUSE IS UN OCCUPIED. 2.) NEW SERVICE REQUIRE A NEW GROUNDING SYSTEM 2 GROUND RODS, A WATER AND GAS BOND. 3.) BRANCH CIRCUITS CANNOT BE RUN IN SAME COMPARTMENTS AS SERVICE ENTRANCE CONDUCTORS, APPEAR SERVICE ENCLOSURE HAS BEEN CHANGED ISOLATION SECTION REMOVED. THIS IS THE SECTION WHICH KEEPS PROTECTED AND UNPROTECTED CABLE SEPERATED. 4.) NO ADDRESS LABEL ON SERVICE 5.) NEED 2ND SUPPORT ON RISER WITH IN 3' OF SERVICE 6. 3/4" EMT CONDUITS CANNOT PENETRATE ON TOP SIDE OF SERVICE 7.) NEW BRANCH CIRCUIT WIRING FROM SERVICE TO INSIDE HAS TO BE INSPECTED. FOLLOW UP 5 DAYS NEED TO GET LICENSED CONTRACTOR. |