Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/09/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/25/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR TEMP POWER FOR RELOCATED SERVICE OK CABLE DROP RECALL FOR FINAL AFTER NEW SERVICE TIE-IN. |
| 04/23/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) GROUND ROD IN TRENCH CAN ONLY BE DRIVEN AT 45 MAX PER ART 250 NEC. 2.) BOND WATER AND GAS PIPING TO SERVICE PER 250-104 NEC. |