Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02EL00671

Parcel: 133270720


Addresses:

8041 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/26/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/03/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) SUPPORT 1/2" CONDUIT 2.) CHASE NIPPLE NOT ALLOWED, USE CLOSE NIPPLE WITH LOCKNUTS BOTH SIDES OF ENCLOSURE 250-94.