Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 04/21/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 04/15/2002 |
ELECTRIC - CABLE DROP |
|
Partial Approval |
IVRS - Inspection 0000*1.) HUB ON TOP OF PANEL HAS BOTTOM LOCKING DEVICE INSTALLED BACKWARDS 2.) FINISH KNOCKING OUT CONCENTRICS AT RISER. 3.) THE ACORN CLAMP ON THE GROUND ROD IS TO HAVE THE WIRE PASS THROUGH NOT DOUBLED. 4.) PLEASE FINISH THE WATER BOND CONNECTION. 5.) THE ADDRESS LABEL IS TO BE PREMANENT 6.) PLEASE SUPPORT CONDUIT ABOVE PANEL 7.) PLEASE USE UV RATED TY WRAPS IF USED. 8.) THE BREAKER NEED TO BE LABELED. |