Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
04/21/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
04/15/2002 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection 0000*1.) HUB ON TOP OF PANEL HAS BOTTOM LOCKING DEVICE INSTALLED BACKWARDS 2.) FINISH KNOCKING OUT CONCENTRICS AT RISER. 3.) THE ACORN CLAMP ON THE GROUND ROD IS TO HAVE THE WIRE PASS THROUGH NOT DOUBLED. 4.) PLEASE FINISH THE WATER BOND CONNECTION. 5.) THE ADDRESS LABEL IS TO BE PREMANENT 6.) PLEASE SUPPORT CONDUIT ABOVE PANEL 7.) PLEASE USE UV RATED TY WRAPS IF USED. 8.) THE BREAKER NEED TO BE LABELED.