Permit: T02EL00641

Parcel: 11207146A


Addresses:

2414 N FORGEUS AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/01/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR.
04/05/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245* NOTES STILL NO COMPLIANCE WIHT ITEM #2, #4 GROUND WIRE IS STILL STICKING UP 2" ABOVE GROUND. TRIP HAZARD. A REINSPECTION FEE IS ASSESED AS THIS IS THIRD INSPECTION FOR THE SMAE VIOLATION.
04/04/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NO COMPLIANCE WITH ITEMS #2 & 3.
03/29/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES: 1. INSTALL BOND BUSHINGS WHERE USING CONCENTRIC OK'S WITH REDUCING WASHERS. 250-94 N.E.C. 2. PLEASE BURY # 4 BARE TO GROUND RODS & DRIVE GRND RODS FLUSH WITH GROUND LEVEL (TRIP HAZARD). 3. LB COVER MISSING 4. HOW DID YOU TIE IN CONDUCTORS BEHIND ATTIC VENT?