Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/05/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR INCREASE OK CABLE DROP. |
| 03/29/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES: 1. BOND GAS PIPE 250-104 2. INSTALL PERMANENT ADDRESS LABEL PER 230-70 # 9287 CITY ORD. 3. USE MIN 1/4 BOLTS TO SUPPORT RISER, 110-12, 110-3, 90-4, & TEP. REQUIREMENTS. |