Permit: T02EL00630

Parcel: 116120260


Addresses:

901 N GRANDE AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/21/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
04/30/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) PLEASE PROVIDE COVER PLATE FOR MIXER 2.) THE OUTSIDE PANEL NEEDS TO BE LABELED FOR BREAKERS 3.) PLEASE LABEL ALL PANELS ON COVERS 4.) AN APPROVED HOLD DOWN DEVICE FROM THE MANFACTURE IS NEEDED OUTSIDE PANEL. 5.) A CHASE NIPPLE IS NOT APPROVED FOR USE WITH A L.B. PLEASE USE APPROVED FITTING. 6.) PLEASE TIGHTEN, RECONNECT AND RE SUPPORT CONDUIT FITTINGS OUTSIDE BY COMPRESSOR ON ROOF.
04/10/2002 ELECTRIC - FINAL Partial Approval 1.) PLEASE TIGHTEN ALL COMPRESSION FITTINGS 2.) THE GUTTERS NEED TO BE BONDED 250.96 3.) IF A BREAKER IS USED AS A BACK FED DEVICE IT IS REQUIRED TO HAVE A MANUFACTORS HOLD DOWN DEVICE 384-16. WORK LOOKS REAL GOOD AND IS PROGRESSING NICE. THANK YOU.