Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/21/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 04/30/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLEASE PROVIDE COVER PLATE FOR MIXER 2.) THE OUTSIDE PANEL NEEDS TO BE LABELED FOR BREAKERS 3.) PLEASE LABEL ALL PANELS ON COVERS 4.) AN APPROVED HOLD DOWN DEVICE FROM THE MANFACTURE IS NEEDED OUTSIDE PANEL. 5.) A CHASE NIPPLE IS NOT APPROVED FOR USE WITH A L.B. PLEASE USE APPROVED FITTING. 6.) PLEASE TIGHTEN, RECONNECT AND RE SUPPORT CONDUIT FITTINGS OUTSIDE BY COMPRESSOR ON ROOF. |
| 04/10/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
1.) PLEASE TIGHTEN ALL COMPRESSION FITTINGS 2.) THE GUTTERS NEED TO BE BONDED 250.96 3.) IF A BREAKER IS USED AS A BACK FED DEVICE IT IS REQUIRED TO HAVE A MANUFACTORS HOLD DOWN DEVICE 384-16. WORK LOOKS REAL GOOD AND IS PROGRESSING NICE. THANK YOU. |