Permit: T02EL00626

Parcel: 135083620


Addresses:

7335 E JUAREZ ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/03/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/27/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PLEASE CORRECT THE FOLLOWING 1.) MARK THE CKT. BRKR'S WITH AREA SERVED/INDEX 2.) INSTALL CKT. BRKR. BLANK. 3.) TERMINATE THE LB ONTO THE PANEL USING A SHORT THREADED NIPPLE & LOCKNUTS. THE USE OF CHASE NIPPLES FOR THIS PURPOSE IS NO LONGER ACCEPTABLE. RECENT INFO. FROM NEC NFPA HAS DETERMINED THAT THE TAPERED SHOULDER ON THE CHASE NIPPLE DOES NOT PROVIDE GOOD METAL TO METAL CONTACT AND THEREFORE POOR GROUND CONTINUITY.