Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/03/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/27/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PLEASE CORRECT THE FOLLOWING 1.) MARK THE CKT. BRKR'S WITH AREA SERVED/INDEX 2.) INSTALL CKT. BRKR. BLANK. 3.) TERMINATE THE LB ONTO THE PANEL USING A SHORT THREADED NIPPLE & LOCKNUTS. THE USE OF CHASE NIPPLES FOR THIS PURPOSE IS NO LONGER ACCEPTABLE. RECENT INFO. FROM NEC NFPA HAS DETERMINED THAT THE TAPERED SHOULDER ON THE CHASE NIPPLE DOES NOT PROVIDE GOOD METAL TO METAL CONTACT AND THEREFORE POOR GROUND CONTINUITY. |