Permit: T02EL00618

Parcel: 140103090

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T02EL00618

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
04/19/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
04/15/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*1.) PLEASE STRAP GROUNDING ELECTRODE CONDUCTOR TO PEDISTALL. 2.) A PERMENT METAL ADDRESS LABEL IS NEEDED ALSO YOU NEED FULL ADDRESS. 3.) GROUND RODS CAN NOT BENT. PLEASE INSTALL AS PER CODE. 4.) PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR.
04/09/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0215*NO UFER GROUND INSTALLED SET RODS PER DRAWING BELOW. DO NOT PLACE CLAMPS LOWER THAN 4 TO 6 INCHES BELOW GRADE. 2" BELOW GRADE 6' OR MORE BETWWEEN RODS. GROUND TERMINATED TO NEUTRAL BAR LUG.THESE SHOULD BE INSPECTABLE IN FUTURE AND REPAIRABLE.