Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T02EL00618
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/19/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
04/15/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*1.) PLEASE STRAP GROUNDING ELECTRODE CONDUCTOR TO PEDISTALL. 2.) A PERMENT METAL ADDRESS LABEL IS NEEDED ALSO YOU NEED FULL ADDRESS. 3.) GROUND RODS CAN NOT BENT. PLEASE INSTALL AS PER CODE. 4.) PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR. | |
04/09/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0215*NO UFER GROUND INSTALLED SET RODS PER DRAWING BELOW. DO NOT PLACE CLAMPS LOWER THAN 4 TO 6 INCHES BELOW GRADE. 2" BELOW GRADE 6' OR MORE BETWWEEN RODS. GROUND TERMINATED TO NEUTRAL BAR LUG.THESE SHOULD BE INSPECTABLE IN FUTURE AND REPAIRABLE. |