Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/24/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP OWNER VERIFIED THAT STRUCTURE WAS EXISTING REPLACED DETERIORATED SIDING DRYWALL, HAS EXISTING PLAN OF OF HOUSE AT TIME OF CONSTRUCTION. |
| 05/20/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PLEASE VERIFY PERMITS FOR REMODEL WORK TO INTERIOR. 2.) BREAKERS TO BE LISTED FOR USE BY MANUFACTURE. 110-3. 3.) WE HAVE MULTIPOLE TERMANANTIONS AT GROUND LUG 110-14. 4.) PLEASE VERIFY BONDING ON METER SIDE OF NIPPLE. 5.) WATER BOND CLAMP TO BE ACCESSABLE 6.) WE HAVE EXPOSED CONDUCTORS IN THE WALL. SHEATHING NEEDS TO EXTEND AT LEAST 1/4" INTO BOX 7.) WE HAVE NON WETHER PROOF FITTINGS IN STALLED IN A DAMP/WET LOCATION. |