Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T02EL00600
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2002 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
03/25/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0215*CORRECTIONS REQUIRED CORRECT & RECALL 1.) TWO STRAPS ARE REQUIRED BELOW ROOF. DO NOT FASTEN STRAPS TO THE "BIRD BOARD" AS THESE BOARDS ARE NON STRUCTURAL AND ARE USED TO VENT THE ATTIC AND KEEP BIRDS OUT. USE UNISTRUT OR SPACERS AND ATTACH STRAPS TO BRICK. SEPARATE BY AT LEAST 6". 2.) USE A SHORT THREADED NIPPLE AND LOCK NUT TO ATTACH LB TO PANEL. THE EMT CONNECTOR IS NOT MEANT TO BE USED FOR THAT PURPOSE. 3.) TWIST THE GROUND/NEUTRAL CONDUCTORS HIGHER ( ON THE SUBPANEL FEEDER CABLE) TO KEEP IT FROM TOUCHING ANY LIVE WIRES IN PANEL. |