Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/13/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR SERVICE UPGRADE CALL FOR FINISH WHEN CHANGE OVER COMPLETE. |
| 05/02/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL PERMANENT ADRESS LABEL PER 230-70NEC. #9287 CITY ORDIN. 2.) BOND WATER & GAS PIPING. 3.) USE MIN 1/4" HARDWARE TO SUPPORT RISER ALSO SEE T.E.P. SPECS 4.) I.D. CIRCUIT BREAKERS 5.) COMPLETE WIRING TO ADDITION THRU 1 1/2" CONDUIT. 6.) RECALL FOR PARTIAL WHEN DONE. |