Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/06/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/02/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR POWER FOR CROSS OVER 1.) PLEASE PROVIDE THE PAPER WORK FROM GFI TEST. 2.) PLEASE RECALL AFTER CROSSOVER |
| 04/29/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) A SPLIT BOLT IS ONLY A RUN & A TAP. PLEASE PROVIDE LUGS AS NECESSARY. 2.) BREAKER NEEDS TO BE LABELED. 3.) GFI TESTING IS REQUIRED 230-95. |
| 04/26/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* 1.) PLEASE PROVIDE A LETTER ON COMPANY LETTER HEAD VERIFING TORQUE VALVES. 2.) PLEASE HAVE AN ELECTRICAN AVAILIABLE FOR INSPECTION TO OPEN UP SERVICE EQUIPMENT. |