Permit: T02EL00577

Parcel: 115151450


Addresses:

2311 N 14TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/06/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/02/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TO CLEAR POWER FOR CROSS OVER 1.) PLEASE PROVIDE THE PAPER WORK FROM GFI TEST. 2.) PLEASE RECALL AFTER CROSSOVER
04/29/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) A SPLIT BOLT IS ONLY A RUN & A TAP. PLEASE PROVIDE LUGS AS NECESSARY. 2.) BREAKER NEEDS TO BE LABELED. 3.) GFI TESTING IS REQUIRED 230-95.
04/26/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000* 1.) PLEASE PROVIDE A LETTER ON COMPANY LETTER HEAD VERIFING TORQUE VALVES. 2.) PLEASE HAVE AN ELECTRICAN AVAILIABLE FOR INSPECTION TO OPEN UP SERVICE EQUIPMENT.