Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/28/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 03/19/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0215*1.) CORRECT & RECALL 1.) THE SERVICE ENTRANCE. CONDUCTORS MUST BE LISTED AND MARKED ON THE SURFACE AS"SUNLIGHT RESISTANT." LEAVE A SAMPLE WHERE I CAN SEE THE MARKING ON THE INSULATION. 2.) THE GROUND WISE ON THE WATER PIPE MUST BE CLAMPED ON THE HOUSE SIDE." (WHERE THE PIPE ENTERS THE WALL). 3.) A MINIMUM OF TWO CLAMPS MUST BE INSTALLED ON THE RISER CONDUIT. ADD ONE NEAR THE TOP OF THE PANEL. 4.) MARK THE 2P 50A C/B WITH AREA OR ITEM IT PROTECTS THANKS. |