Permit: T02EL00547

Parcel: 117031580


Addresses:

845 N QUEEN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/20/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*APPROVED OK TO CLEAR FINAL.
03/19/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) THE #4 GROUNDING ELECTRODE CONDUCTOR MUST BE CONNECTED TO THE NEUTRAL AT THE SERVICE AS DESCRIBED IN THE 99 NEC SECTION 250-24. YOU NEED TO USE A MAIN BONDING JUMPER (#4) FROM THE LOCATION AT WHERE YOUR GROUNDING ELECTRODE CONDUCTOR IS TERMINATED TO THE NEUTRAL LUG ALL OF THIS TO BE ACCOMPLISHED IN COMPARTMENT BELOW 221 W 2ND. 2.) ALL NEUTRALS TO BE CONNECTED AT NEUTRAL BAR.