Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/20/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*APPROVED OK TO CLEAR FINAL. |
| 03/19/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) THE #4 GROUNDING ELECTRODE CONDUCTOR MUST BE CONNECTED TO THE NEUTRAL AT THE SERVICE AS DESCRIBED IN THE 99 NEC SECTION 250-24. YOU NEED TO USE A MAIN BONDING JUMPER (#4) FROM THE LOCATION AT WHERE YOUR GROUNDING ELECTRODE CONDUCTOR IS TERMINATED TO THE NEUTRAL LUG ALL OF THIS TO BE ACCOMPLISHED IN COMPARTMENT BELOW 221 W 2ND. 2.) ALL NEUTRALS TO BE CONNECTED AT NEUTRAL BAR. |