Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - RECONNECT
Permit Number - T02EL00540
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2002 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection 0000*1.) SERVICE UPGRADE TO BE A NEW PERMIT. MEET WITH CONTRACTOR TO DISCUSS PROJECT. | |
03/19/2002 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*PLEASE USE APPROVED WIRING METHODS FOR LIGHTING IN BACKROOM ALSO USE APPROVED LIGHT FIXTURES 2.) PLEASE WIRE WATER HEATER AS PER CODE CORDS ARE NOT APPROVED. 3.) PHYSICAL PROTECTION IS NEEDED FOR EXPOSED ROMEX CABLE. 4.) PLEASE USE AN APPROVED WIRING METHOD FOR COOLER 5.) A PERMIT NEEDS TO BE OBTAINED FOR SHOWER IN BACK ROOM. 6.) SERVICE NEES TO HAVE WORKING CLEARANCES INFRONT OF. 7.) SERVICE IS IN DETERIORATED CONDITION AND NOT ACCESSABLE FOR MAINTANCE PLEASE UPGRADE YOUR SERVICE. | |
03/18/2002 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999* |