Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
04/07/2002 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
03/17/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999* 1.) PERMANENT ADDRESSING NEED TO BE POSTED ON BUILDING 2.) SMOKE DETECTORS NEED TO BE INSTALLED AS PER MANUFACTURES DIRECTIONS 3.) PLUMBING FIXTURES NOT INSTALLED AT THIS TIME 4.) A MECHANICAL PERMIT IS REQUIRED FOR NEW DUCT WORK AND UNIT INSTALLATION. 5.) GROUNDING AND TERMATIONS ARE NEEDED AT FIXTURES 6.) WE HAVE GROUNDED RECETACLES ON AN UNDERGROUND SYSTEM. 7.) PLEASE USE A SURFACE MOUNTED BOX THAT IS LISTER FOR USE ALSO WITH WIREMOLD. 8.) SUB PANEL TO USE GROUND BAR LISTED FOR USE Y THE MANUFACTURER ALSO PLEASE AS PER LISTING
INSTRUCTION 9.) MULTIPLE TERMANATIONS AT NEUTRAL LUG IN SERVICE.