Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/20/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR |
| 03/18/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0220*CORRECTION REQUIRED: 1.) THE GROUND WIRE AT THE COLD WATER PIPE MSUT BE A MOVED TO THE HOUSE SIDE OR ADD CLAMPS & WIRE TO STRAP AROUND UNIONS. 2.) THE "L B" AND THE BELL BOX AT THE PANEL MUST BE TERMINATED AT THE BOX/PANEL WITH SHORT OR ALL THREAD NIPPLES & LOCKNUTS. THE "CHASE NIPPLES" DO NOT PROVIDE A GOOD CONTINUITY BETWEEN FITTINGS & THE METAL OF THE PANEL. 3.) CODE REQUIRES A MINIMUM OF TWO (2) STRAPS ON THE RISER CONDUIT BELOW THE ROOF LINE. |