Permit: T02EL00521

Parcel: 135111160


Addresses:

7606 E 35TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/20/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR
03/18/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0220*CORRECTION REQUIRED: 1.) THE GROUND WIRE AT THE COLD WATER PIPE MSUT BE A MOVED TO THE HOUSE SIDE OR ADD CLAMPS & WIRE TO STRAP AROUND UNIONS. 2.) THE "L B" AND THE BELL BOX AT THE PANEL MUST BE TERMINATED AT THE BOX/PANEL WITH SHORT OR ALL THREAD NIPPLES & LOCKNUTS. THE "CHASE NIPPLES" DO NOT PROVIDE A GOOD CONTINUITY BETWEEN FITTINGS & THE METAL OF THE PANEL. 3.) CODE REQUIRES A MINIMUM OF TWO (2) STRAPS ON THE RISER CONDUIT BELOW THE ROOF LINE.