Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/20/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR |
| 03/14/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* 1.) PLEASE OBTAIN A PERMIT FOR INSTALLATION OF A/C UNIT 2.) ALL CIRCUIT BREAKERS NEED TO BE LABELED 3. PLEASE INSTALL ALL CIRCUIT BREAKERS 4.) ALL STRANDS OF CONDUCTOR NEED TO BE TERMANATED UDNER BREAKER SCREW. 5.) AN APPROVED FITTING IS REQUIRED AT L.B. A CHASE NIPPLE IS NOT APPROVED. 6.) PROVIDE PROTECTION WHERE NM CABLES ENTER CONDUIT SLEEVE. |