Permit: T02EL00517

Parcel: 107141020


Addresses:

245 E ALTURAS ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/08/2002 ELECTRIC - SERVICE UPGRADE Approved
04/08/2002 ELECTRIC - SERVICE UPGRADE Approved
03/18/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1. 1/4" HARDWARE MINIMUM IS NEEDED FOR ANEL & RISER SUPPORT. 2. BREAKEERS NEED TO BE LABELED. 3. IF CONDUTORS ARE ALUMINUM PLEASE PROVIDE AN ANTI-OXIDE COMPOUND. 4. PLEASE VERIFY SIZE OF GROUDING ELECTRODE CONDUCTOR OR PROTECT FROM PHYSICAL DAMAGE PER CODE. 250-64 (B)
03/17/2002 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection 0000*