Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 04/03/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 03/27/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0245*NOTES* 1. MUST USE SEALING LOCKNUT ON 3/4" PENETRATION THAT WAS RELOCATED FROM METERING COMP. SEALING LOCKNUTS REQUIRED FOR PENETRATIONS ABOVE BUSS LINE TO INSURE WATER SEAL. |
| 03/19/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL BOND BUSHING ON 1 1/4" CONNECTOR WHERE USING CONCENTRIC KO. 250-94NEC. 2. USE MIN 1/4" BOLTS TO ANCHOR OR SUPPORT RISER. 110-12 & PER TEP SPECS. 3.) CIRCUIT RUN THRU METERING COMPARTMENT NOT ALLOWED. 230-7 NEC. 4.) SUPPORT 1 1/4 CONDUIT WITHIN 3' OF ENCLOSURE 348-13 NEC. |