Permit: T02EL00502

Parcel: 133224110


Addresses:

6910 E KINGSTON DR

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
04/03/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
03/27/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0245*NOTES* 1. MUST USE SEALING LOCKNUT ON 3/4" PENETRATION THAT WAS RELOCATED FROM METERING COMP. SEALING LOCKNUTS REQUIRED FOR PENETRATIONS ABOVE BUSS LINE TO INSURE WATER SEAL.
03/19/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0245*1.) INSTALL BOND BUSHING ON 1 1/4" CONNECTOR WHERE USING CONCENTRIC KO. 250-94NEC. 2. USE MIN 1/4" BOLTS TO ANCHOR OR SUPPORT RISER. 110-12 & PER TEP SPECS. 3.) CIRCUIT RUN THRU METERING COMPARTMENT NOT ALLOWED. 230-7 NEC. 4.) SUPPORT 1 1/4 CONDUIT WITHIN 3' OF ENCLOSURE 348-13 NEC.