Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/28/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK CLEAR. SER. INCREASE #3 NEW SERVICE. |
| 03/15/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1. PLEAE HAVE PERMIT CORRECTEC THRU PERMIT COUNTER TO INDICATE METER LOOPS 1,2, & 3. 2. THE BASE AT THE 3 SERVICES PRESENTS A TRIPPING HAZARD FOR ANYONE WHO HAS TO INSPECT, EXAMINE, OR MAINTERANCE ANY OF THE SERVICES. THIS SITUATION MUST BE MADE SAFE , A FLAT SURFACE ISREQUIRED FOR ANYONE TO STAND SAFELY IN FRONT OF SERVICE. 3. PROVIDE A LOAD CALCULATION SHEET( CAN BE FAXED TO MY OFFICE AT 791-4340, ATTN: RAY MAJUTA) THERE IS A QUESTION ON UNIT # 2 BEING A 100AMP SERVICE & HAVING 2-50A. 2 POLE BREAKERS, 2- 30 AMP 2 POLE & 6 20 A 1 POLE BREAKERS. 4. CANNOT VERIFY GAS & WATER BOND. 5. THE SITUATION WHERE THE 2" RISER IS CUT INTO THE RAIN GUTTER IS ONE WHICH HAS BE BE CORRECTED. DURING RAN A CONCENTRATION OF WATER WILL POUR OVER THE SERVICE. 6. PLEASE MEET INSPECTOR TO OPEN GUTTER A NEXT INSPECTION. ON REQUEST LEAVE A CALL AHEAD NUMBER OR CALL 791-5550 EX 136 BETWEEN 7-8 ON DAY OF REQUESTED INSPECTION. TO SET UP A MEETING. |