Permit: T02EL00493

Parcel: 123120300


Addresses:

1320 E HAMPTON ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T02EL00493

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
01/08/2003 ELECTRIC - SERVICE UPGRADE Partial Approval 1.) STRAP ALL #4 COPPER ON TO BUILDING
2.) CALL FOR FINAL ONCE UPGRADE COMPLETED.
HOLD CLEARANCE TO TEP TILL. OWNER REQUEST RELEASE.
03/14/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0215* THE FOLLOWING CORRECTION ARE REQUIRED 1.) THE RISER CONDUIT MUST BE SRAPPED/SUPPORTED IN TWO PLACES. 2.) AT LEAST TWO FEET OF SLACK MUST BE LEFT ON THE RISER CABLES FOR CONNECTION TO TEP LINES. 3.) THE COLD WATER AND GAS PIPES MUST BE BONDED AND GROUNDED TO THE PANEL. 4.) THE GROUND WIRE MUST BE ATTACHED TO RODS WITH GROUND ROD CLAMPS NOT TWO PIECE PIPE CLAMPS. 5.) THE ADDRESS ON THE MAIN PANEL MUST BE MADE OF PERMANENT METALLIC MATERIALS RESISTANT TO THE WEATHER & SUN. MAGIC MARKER IS NOT ACCEPTED.6.) MARK THE CIRCUIT BREAKERS WITH AREA SERVED.