Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T02EL00493
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2003 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
01/08/2003 | ELECTRIC - SERVICE UPGRADE | Partial Approval | 1.) STRAP ALL #4 COPPER ON TO BUILDING 2.) CALL FOR FINAL ONCE UPGRADE COMPLETED. HOLD CLEARANCE TO TEP TILL. OWNER REQUEST RELEASE. |
|
03/14/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0215* THE FOLLOWING CORRECTION ARE REQUIRED 1.) THE RISER CONDUIT MUST BE SRAPPED/SUPPORTED IN TWO PLACES. 2.) AT LEAST TWO FEET OF SLACK MUST BE LEFT ON THE RISER CABLES FOR CONNECTION TO TEP LINES. 3.) THE COLD WATER AND GAS PIPES MUST BE BONDED AND GROUNDED TO THE PANEL. 4.) THE GROUND WIRE MUST BE ATTACHED TO RODS WITH GROUND ROD CLAMPS NOT TWO PIECE PIPE CLAMPS. 5.) THE ADDRESS ON THE MAIN PANEL MUST BE MADE OF PERMANENT METALLIC MATERIALS RESISTANT TO THE WEATHER & SUN. MAGIC MARKER IS NOT ACCEPTED.6.) MARK THE CIRCUIT BREAKERS WITH AREA SERVED. |