Permit: T02EL00484

Parcel: 117200290


Addresses:

260 S CHURCH AV


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL00484

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
12/12/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
12/12/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*1.) TRASFORMER LABELED
2.) SW'S LABELED
3.) 15KV FEEDERS FROM TCC TO FIRE & POLICE EIT TESTED & MEGGED 4.) NEW 15 KVA TRANSFORMERS AT FIRE 13.8 KU TO 208V 3 DIAMETER AND POLICE 13.8 KV TO 480V 3/0 TESTED MY ETI.
11/13/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) NEXT INSPECTION REC 2 FOR CUT OVER
10/23/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) J-BOX BETWEEN 1ST FUSED DISCONNECT MEANS AND 2ND NF DISCONNECT OK 2.) CLEARANCE FOR POWER CHANGE OVER TO BE GIVEN ONCE TRANSFORMERS PER POLICE & FIRE STATIONS SET AND INSPECTED, ALSO ONCE REPLACE FROM TRANSFORMERS TO BLDG CHECKED.
10/21/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) TRANS 1000 KW 13,800/480 SEC, ETI TEST ON TRANS AND CABLE AND TWO TRANS AT FIRE & POLICE OK SUDMIT RECORDS OF TEST. 2.) I D FUSED DISION 13.8 KU AT CENTER GOING TO FIRE AND POLICE. 3.) J-BOX IS GROUND TIED TO BOX PLEASE OPEN TO VERIFY 4.) NON FUSED DISCONNECT ID SECTION. 5.) FOR FINAL PROVIDE TEST RESULTS FOR EQUIPMENT TRANS, CABLE SECTION CAN. 6.) WILL NEED TO SEE FINAL CONNECTION BETWEEN NEW 150 & 750 TRANS TO BUILDINGS. 7.) CHECK ON TIE IN TO UFER CABLE AT IN AN HOLES ELECT.