Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL00484
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
12/12/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*1.) TRASFORMER LABELED 2.) SW'S LABELED 3.) 15KV FEEDERS FROM TCC TO FIRE & POLICE EIT TESTED & MEGGED 4.) NEW 15 KVA TRANSFORMERS AT FIRE 13.8 KU TO 208V 3 DIAMETER AND POLICE 13.8 KV TO 480V 3/0 TESTED MY ETI. |
|
11/13/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) NEXT INSPECTION REC 2 FOR CUT OVER | |
10/23/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) J-BOX BETWEEN 1ST FUSED DISCONNECT MEANS AND 2ND NF DISCONNECT OK 2.) CLEARANCE FOR POWER CHANGE OVER TO BE GIVEN ONCE TRANSFORMERS PER POLICE & FIRE STATIONS SET AND INSPECTED, ALSO ONCE REPLACE FROM TRANSFORMERS TO BLDG CHECKED. | |
10/21/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) TRANS 1000 KW 13,800/480 SEC, ETI TEST ON TRANS AND CABLE AND TWO TRANS AT FIRE & POLICE OK SUDMIT RECORDS OF TEST. 2.) I D FUSED DISION 13.8 KU AT CENTER GOING TO FIRE AND POLICE. 3.) J-BOX IS GROUND TIED TO BOX PLEASE OPEN TO VERIFY 4.) NON FUSED DISCONNECT ID SECTION. 5.) FOR FINAL PROVIDE TEST RESULTS FOR EQUIPMENT TRANS, CABLE SECTION CAN. 6.) WILL NEED TO SEE FINAL CONNECTION BETWEEN NEW 150 & 750 TRANS TO BUILDINGS. 7.) CHECK ON TIE IN TO UFER CABLE AT IN AN HOLES ELECT. |