Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T02EL00453

Parcel: 106051190

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL00453

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/24/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000* OK TO CLEAR INCREASE OK CABLE DROP.
05/22/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) GROUNDING ELECTRODE CONDUCTOR TO BE 1/0 PER PLAN. 2.) INSTALL RISER. 3.) I.D. CIRCUIT BREAKERS.