Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/12/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/07/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1. INSTALL PERMANENT ADDRESS LABEL ON SERVICE PER ART 230-70 N.E.C. 9287 CITY ORDINANCE. 2.) GROUND RODS TO BE MIN 6' APART PER ART 250 N.E.C. 3.) PHASE CONDUCTORS IN PANEL NOT COLOR CODED PROPERLY. 4.) WATER BOND CONNECTION AT PIPE SEEMS TO BE DETERIORATED, EXISTING CLEAN AND RE-ATTACH. |