Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/10/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/03/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) CHASE NIPPLE ON 3/4" LB ENTERING ENCLOSURE NOT AN APPROVED WIRING METHOD. MUST USE CLOSE NIPPLE WITH LOCKNUTS AND BOND BUSHINGS WHERE USING CONCENTRIC KO'S 250-94 NEC. 2. ) BOND GAS PIPING 250-104 N.E.C. |