Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/08/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR
03/06/2002 ELECTRIC - SERVICE UPGRADE Denied 1.) GROUND CLAMPS AT GROUND RODS TO HAVE #4 COPPER PASS THUR IT ONCE NOT DOUBLED 2.) WATER BOND CLAMP TO HAVE #4 COPPER PASS THUR HOLE WITH BOLT NOT UNDER CLAMP. 3.) SERVICE HAST TO HAVE A PERMANENT ADDRESS DO NOT USE MARKER PEN. 4.) THE 2" STRAP HOLDING RISER JUST BELOW ROOF HAS TO GO ALL THE WAY THRU TO THE LEDGER ON TOP OF BLOCK 5.) THE 3/4" EMT CONNECTORS GOING FROM THE LB'S TO THE PANEL ARE USED INCORRECTLY, USE CLOSED NIPPLE WITH LOCK NUTS ONE INSIDE ONE OUTSIDE. PS DO NOT USE SET SCREW EMT FITTINGS OUTSIDE WHERE OLD SERVICE IS THEY ARE NOT RATED FOR OUTSIDE.