Permit: T02EL00429

Parcel: 113080360


Addresses:

820 E ADELAIDE DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/08/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/02/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) TYPE NM ROMEX NOT APPROVED FOR UNDERGROUND USE. 2.) INSTALL LOCKNUT ON CHASE NIPPLE TO ENSURE ELECTRICAL CONTINEITY. 3.) INSTALL BREAKER BLANK ON DEADFRONT OF PANEL. 4.) GROUNDS RODS CAN ONLY BE DRIVEN AT MAX 45 ANGLE. MUST BE SPACED 6' APART MIN.