Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T02EL00420
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2002 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000*TEP MAY REQUIRE YOU TO FURNISH A CLEVIS TO ATTACH THE SERVICE WIRES CHECK WITH THEIR CUSTOMER SERVICE. | |
| 03/26/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0215* THE CORRECT WAY TO INSTALL THE GROUND SYSTEM IS PER DIAGRAM BELOW SET THE GROUND RODS 2" BELOW GROUND LEVEL. YOUR 2" PIPE IS LEANING TO THE RIGHT. YOU COULD HAVE SET YOUR PANEL AT STANDARD 48" GROUND TO BOTTOM. WOOD BACKBOARD IS NOT REQUIRED. | |
| 03/06/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245*1.) 2 GROUND RODS REQUIRED 6' MIN SPACING APART, PER ART 250 N.E.C. SPACING APART, PER ART 250 N.E.C. 2.) PERMANENT ADDRESS REQUIRED LABEL. TO BE SCREWED OR RIVITED TO ENCLOSURE PER ART 230-70 N.E.C. #9287 CITY ORDINANCE. 3.) NEW SERVICE CANNOT BE LOCATED OVER GAS METER MUST HAVE 30" HORIZONTAL AND 36" WORKING SPACE IN FRONT TO PER 110-26 N.E.C. GROUND. 4.) WORK TO BE DONE BY OWNER/OCCUPANT OR C-11 LICENSED CONTR. DWELLING NOT OCCUPIED. 5.) COLOR CODING OF RISER CONDUCTORS |