Permit: T02EL00404

Parcel: 113082610


Addresses:

3033 N PARK AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/06/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR.
02/27/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1.) YOU CAN NOT USE A SHEETROCK SCREW FOR GROUNDING 250-8. 2.) SPLICE WRAPS ARE TO BE EQUAL TO CONDUCTOR INSULATION 110-14. 3.) SPLIT BOLT ARE ONLY LISTED FOR 2 CONDUCTORS 4.) ONLY 1 CONDUCTOR PER TERMANAL AT THE NEURTRAL BAR. OK TO COVER PVC CONDUIT.