Permit: T02EL00403

Parcel: 113042250


Addresses:

754 E HOLAWAY DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/17/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR INCREASE UNITS 754 & 756. OK CABLE DROP.
04/12/2002 ELECTRIC - FINAL Denied 1.) PLEASE VERIFY GAS BONDING 2.) A SEALING DEVICE IS REQUIRED FOR FITTING ENTERING ABOVE THE BUSS. 3.) A NON FLEXIBLE RACE WAY IS REQUIRED FOR ENTRANCE TO THE SERVICE AS PER 373-5 (C) EXCEPTION AND A-C FOR NM AND UP CABLES.