Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/22/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/26/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210*1.) NEED SEALING FITTINGS AT PANEL CONNECTOR AT SERVICE 2.) STRAP GROUND WIRE FIRMLY TO WALL STRAIGHTEN GROUND WIRE ADJACENT TO GAS METER. FOR FINAL CLEARANCE WILL NEED FINAL APPROVED. |
| 02/28/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |