Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/08/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
|
| 03/06/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 02/28/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) THIS PROJECT IS A DUPLEX AN ADDITIONAL FEE FOR 2ND METER NEED TO BE ADDED TO PERMIT. 2.) PLEASE VERIFY GAS BOND FOR 2ND GAS SERVICE. 3.) PLEASE OPEN UP METER SOCKETS TO VERIFY BONDING DEVICES 250-94. 4.) CONDUIT FILL EXCEEDED PER CODE 310-15 & 310-16. 5.) PLEASE VERIFY " SUN LIGHT RESISTANT" LISTING FOR CONDUCTORS AT RISER 310-8(D) |