Permit: T02EL00363

Parcel: 11014015A


Addresses:

2900 N CRAYCROFT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/26/2002 ELECTRIC - FINAL Approved
06/20/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) COLD WATER BOND NOT SIZED PER NEC. ALSO SEE PLANS. 2.) SEE ITEMS #2 LAST INSP. WRITE UP.
05/29/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) NEED REVISED APPROVED PLANS TO INDICATE CHANGE MADE IN FIELD 2. METAL RACEWAY USED FOR GROUNDING ELECTRODE CONDUCTOR MUST HAVE BOND BUSHINGS AT TERMINATIONS OR PER ART 230-NEC. 3.) BOND WATER PIPING. 4.) EMT CONDUIT MUST BE SUPPORTED WITHIN 3' OF TERMINATION PER 348 NEC.
05/24/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0945*CALL PH# PER MSG. LEFT MSG ON CONTR'S VOICE MAIL, GAVE 1/2 HOUR LEAD TIME ETA. NO SHOW, COULD NOT LOCATE WORK BEING DONE TO INSPECT.