Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/13/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/20/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) ADDRESS LABEL TO BE PERMANENTLY INSTALLED BY RIVITS OR SELF TAPPING SCREWS. SEE ART 230-70 NEC. #9287 CITY OF TUCSON ORDIN. 230-70-B. 2.) GROUND J-BOX PER ART 250-148 270-40 N.E.C. 3.) NEED TO VERIFY GAS & WATER BONDING. 250-104 N.E.C. |